Error messages
CodeMeaning
F0000No fault has occurred.
Overload
 

F01

00Frequency inverter overloaded, check load behaviour. Reduce ramps and speed.
01Frequency inverter overloaded in low output frequency range.
02Frequency inverter overloaded (60 s), check load behaviour.
03Short-term overload (1 s), check motor and application parameters.
Heat Sink
F0200Heat sink temperature too high, check cooling and ventilator.
01Heat sink temperature too cold, check allowed ambient temperature.
Inside
 

F03

00Inside temperature too high, check cooling and ventilator.
01Inside temperature too cold, check allowed ambient temperature.
03Capacitor temperature too high, check cooling and ventilator.
Motor connection
 

F04

00Motor temperature too high or sensor defective, check connection at terminal X12.4.
01Motor circuit breaker tripped, check drive.
02V-belt monitoring reports no load on the drive.
03Phase failure, check motor and wiring.
Output current
 

 

 

 

F05

00Overloaded, check load situation and ramps.
06Motor phase current too high, check motor and wiring.
07Message from phase monitoring, check motor and wiring.
08Message from phase monitoring, check motor and wiring.
09Message from phase monitoring, check motor and wiring.
 

11

Motor still rotates. The motor is still excited and rotates and

–      drive start command applies and the flying start function is deactivated or

–      a device test is tried to start

Internal Error.
F06xxInternal Error. Please contact your Bonfiglioli office.
DC–link voltage
 

 

 

F07

00DC link voltage too high, check deceleration ramps and connected brake resistor.
01DC link voltage too small, check mains voltage.
02Power failure, check mains voltage and circuit.
03Phase failure mains, check mains fuses and circuit.
04Reference DC-Link Limitation 680 too small, check mains voltage.
05Overvoltage brake chopper. Refer to chapter 13.3 “Troubleshooting” (Shut-down).
06Overvoltage motor chopper. Refer to chapter 13.3 “Troubleshooting” (Shut-down).
Electronics voltage
 

F08

01Electronics voltage DC 24 V too low, check control terminal.
04Electronics voltage too high, check wiring of control terminals.
05Fault in the the A/D converter. Remove all external connections (signal terminals etc.) and check if the fault remains

 

 

Error messages
CodeMeaning
  

 

 

06

Voltage supply for optional communication module too low. Communication via bus system faulty.

Disconnect bus system wiring and acknowledge the error message. Check connections and wiring of the bus system.

Replace the communication module if the error occurs, even if the bus system is dis- connected.

If the communication module is replaced and the error occurs, contact the service of BONFIGLIOLI.

Brake chopper
F1010Brake chopper overcurrent. Also refer to chapter 7.10.4 “Brake chopper and brake resist”.
Output frequency
 

F11

00Output frequency too high, check control signals and settings.
01Maximum frequency achieved by control. Check deceleration ramps and connected brake resistor.
Enable
 

 

 

 

 

 

 

 

 

F12

 

01

The STO Diagnosis software recognized a fault in the STO switch-off paths. Check

wiring, connect screens. Check the EMC environment. If the fault remains, exchange the device.

02Fault of the STO diagnosis function. If the device remains after a new start up, ex- change the device.
04Internal Fault. Contact the BONFILGLIOLI customer service.
05Enable signals STOA and STOB were not actuated at the same time, but with a high time offset. Check the circuitry of the enable input signals.
06The voltage of the STO signals is too low. Check the dimensioning of the DC 24 V sup- ply, that supplies the STO inputs.
07The STO diagnosis software was not able to detect a clear defined STO level. Check the wiring and STO triggering device. Ensure, that clear signal levels can be received (DC 0 V / DC 24 V). If the fault persists, check if the fault persists with another drive.
08The STO diagnosis software has recognized that the STO signal levels of the device don’t correlate to each other at different measurement points. Check the wiring, put the screens on correctly. If the fault persists, exchange the device.
09The STO diagnosis software recognized that an STO signal is too high inside the de- vice. Check the wiring; apply a clear defined signal level (0V / 24 V). If the fault per- sists, exchange the device.
Motor connection
F1300Earth fault on output, check motor and wiring.
10Minimum current monitoring, check motor and wiring.
Control connection
 

 

 

 

 

F14

01Reference value on multifunctional input 1 faulty, check signal.
02Reference value on multifunctional input 2 faulty, check signal.
07Overcurrent on multifunctional input 1, check signal.
08Overcurrent on multifunctional input 2, check signal.
09No actual value for technology controller. Missing actual value was reported according to setting for Operation mode actual value failure 440.
50Temperature measurement with KTY measuring resistor defective. Check signal and measuring resistor.
 

54

External error; drive responded according to parameter setting for Operation mode ext.

error 535. Error was triggered via the logic signal or digital input signal assigned to parameter External error 183.

Modbus and VABus
F2010Communication error according to parameter X21: VABus Watchdog-Timer 1502.
11Communication error according to parameter CM: VABus Watchdog Timer 413.

 

 

Error messages
CodeMeaning
CANopen
 

 

 

 

 

 

F20

21CAN Bus OFF
22CAN Guarding
23Error state
24SYNC error (SYNC timing)
25CAN error state
26RxPDO1 length error 

Number of received bytes differs from mapping.

27RxPDO2 length error
28RxPDO3 length error
2ARxPDO1 TimeoutRxPDO was not received in expected time.

Ensure, that the RxPDO can be received in the set up “Event time” (Subindex 5).

2BRxPDO2 Timeout
2CRxPDO3 Timeout
DeviceNet
F205xDeviceNet Fault. Please check DeviceNet manual.
Profibus
F206xProfibus Fault. Please check Profibus manual.
Internal Error.
F207Internal Error. Please contact your Bonfiglioli office.
System bus
F21nnFault message on system bus master when a fault at system bus slave occurs, nn = node-ID of slave (hex)
 

 

F22

00Communication fault, system bus, timeout sync-telegram
01Communication fault, system bus, timeout RxPDO1
02Communication fault, system bus, timeout RxPDO2
03Communication fault, system bus, timeout RxPDO3
10Communication fault, system bus, bus-off
CANopen
F23nnHeartbeat error, nn = triggering node.
CM module recognition
F2400Unknown CM module. Check compatibility firmware and CM module.
Industrial Ethernet
F27nnIndustrial Ethernet Fault. Please check manual of used Ethernet module.
EtherCAT
F28nnEtherCAT fault.
User Error
F303nUser triggered Error of Internal PLC. Please check the application manual VPLC.
Optional components
F0B13Assembly of communication module was done without disconnection of mains supply. Disconnect mains supply.
Internal monitoring
F0C40After 6 warm starts in less than 3 minutes this fault is triggered, due to the expectation that a faulty programming of the PLC or the function table is at hand. Additionally the

PLC / Function table is stopped (P. 1399 = 0 only in RAM).